Existing pump - Circulation Pump curve
Replacement pump - High Efficiency Premium Smart Exchange sheet
Comment
Product information
Stratos GIGA2.0-I 100/1-8/1,1
High-efficiency in-line pump with EC motor of energy efficiency class IE5 in accordance with IEC 60034-30-2, hydraulics with minimum efficiency index MEI ≥ 0.7 and electronic power adjustment in glanded pump construction. The pump is configured as a single-stage low-pressure centrifugal pump with flange connection and mechanical seal. The Stratos GIGA2.0-I has been predominantly designed for pumping heating water (acc. to VDI 2035), cold water and water-glycol mixtures without abrasive substances in heating, air-conditioning and cooling systems.
Design
- Single-stage low-pressure centrifugal pump with one-piece shaft in monobloc design
- Spiral housing in in-line design (suction and pressure ports with the same flanges in a line)
- PN 16 flange – drilled according to EN 1092-2
- Pressure measuring connections (R 1/8) for mounted differential pressure sensor (version ...-R1 without differential pressure sensor)
- Pump housing and motor flange with cataphoretic coating as standard
- Mechanical seal for pumping water up to Tmax. = +140 °C. A glycol admixture of 20 % to +40 % by volume is permitted up to T ≤ +40 °C. An alternative mechanical seal must be provided in water-glycol mixtures with glycol proportions > 40 % up to maximum 50 % by volume and a fluid temperature of > +40 °C up to maximum +120 °C or fluids other than water.
- Connection voltages: 3~440 V ±10 % 50/60 Hz; 3~400 V ±10 % 50/60 Hz; 3~380 V ±10 % 50/60 Hz
- Permanent, automatic performance adaptation to system requirements without setpoint specification Wilo Dynamic Adapt plus (factory setting).
- Constant temperature (T-const.)
- Constant differential temperature (dT-const.)
- Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple secondary pumps (Multi-Flow Adaptation).
- Constant volume flow (Q-const.)
- Variable differential pressure (dp-v) with the option to set the nominal duty point Q and H
- Constant differential pressure (dp-c)
- Differential pressure control (dp-c) to a remote point in the pipe network (index circuit evaluator)
- Constant speed (n-const.)
- User-defined PID control
- Heat quantity measurement
- Cooling quantity measurement
- Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.)
- Operating modes of twin-head pump: Main/standby operation, efficiency-optimised parallel operation for dp-c and dp-v
- Pump automatically deactivates when no flow is detected (No-Flow Stop)
- Switchover between heating and cooling mode (automatic, external or manual)
- Ability to save and restore configured pump settings (3 restoration points)
- Fault and warning messages shown in plain text with advice on resolving the issue
- Integrated full motor protection
- Control mode currently set
- Current setpoint
- Current volume flow (only if a differential pressure sensor is connected)
- Current fluid temperature (only if temperature sensor is connected)
- Current power consumption
- Cumulative electric consumption
- 4 configurable analogue inputs: 0 – 10 V, 2–10 V, 0 – 20 mA, 4 – 20 mA and commercially available PT1000 (only on two analogue inputs); +24 V DC power supply
- 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
- 2 configurable signal relays for run signals and fault messages
- Slot for Wilo-CIF modules with interfaces for building automation (BA) (optional accessories: CIF modules Modbus RTU, BACnet MS/TP, LON, PLR, CAN)
- Wilo Net as a Wilo system bus for communication between Wilo products, e.g. Multi-Flow Adaptation; twin-head pump operation and Wilo-Smart Gateway
- Automatic emergency operation with definable pump speed for exceptional circumstances, e.g. bus communication or sensor value malfunction
- Rotatable, graphic colour display (4.3 inches) with one button manual operation level
- Bluetooth interface via Wilo-Smart Connect module BT
- Use the Wilo-Assistant app to read and set operating data and –among other things– set up a commissioning protocol through the Bluetooth interface
- Integrated dual pump management (twin-head pumps are prewired) when using 2 single pumps as twin-head pump unit (connection via Wilo Net)
- Cable break detection when using an analogue signal (in connection with 2 – 10 V or 4 – 20 mA)
- Time stamp for error/warnings and historical operating data
- Continuous operating data memory
- Standard condensate drainage holes in the motor housing (closed upon delivery)
- Air vent valve on the lantern
- Pump
- Wilo-Smart Connect module BT
- Threaded cable glands with sealing inserts
- Installation instructions (short summary) and declaration of conformity
- 3 mounting brackets with fixation material for installation on a base
- Blind flanges for twin-head pump housing
- Installation aid for mechanical seal (incl. mounting bolts)
- CIF module PLR
- CIF module LON
- CIF module BACnet MS/TP
- Modbus RTU CIF module
- CIF module CANopen
- CIF module Ethernet Multi-protocol (Modbus TCP, BACnet/IP)
- Differential pressure sensor DDG 2 – 10 V
- Temperature sensor PT1000 AA
- Sensor sleeves for the installation of temperature sensors in the pipe