1 replacement option found

Existing pump - Circulation

Brand Flygt, ITT, Lowara, Xylem
Product name AL 80/2-156
Overall length 360 mm
Mains connection 3x400 V
Pipe Connection DN 80 PN10

Replacement pump - Conventional Exchange sheet

Product name Atmos GIGA-I 65/130-5,5/2
Item no. 2220172
MEI ≥ 0,4
IE 3
Overall length 430 mm
Mains connection 3x400 V
Pipe Connection DN 65 PN16
Rated Current 9,9 A
Nominal power P2 5,5 kW
Fluid temperature range -20 - +140 °C

Comment

**NOTE** Modification of piping.

Product information
Atmos GIGA-I 65/130-5,5/2

Atmos GIGA-I 65/130-5,5/2
Item no. : 2220172

Design
Glanded pump in in-line design with flange connection.

Application
The pumping of heating water (in accordance with VDI 2035), chilled water and water-glycol mixtures without abrasive substances in heating, chilled water and cooling systems.

Technical data
  • Permitted temperature range of the fluid: -20 °C to +140 °C
  • Max. ambient temperature 40 °C
  • Mains connection 3~400 V, 50 Hz (others on request)
  • Protection class IP55
  • Nominal diameter DN 32 to DN 250
  • Standard version for operating pressure: 13 bar (up to +140 °C) / 16 bar (up to +120 °C)
Materials
  • Pump housing and lantern: Standard: EN-GJL-250;
  • Impeller: Standard: EN-GJL-200; special version: Bronze CuSn 10 stainless steel 1.4408
  • Shaft: 1.4122
  • Mechanical seal: AQEGG; other mechanical seals on request
Construction
Single-stage, low-pressure centrifugal pump in in-line design with:
  • Mechanical seal
  • Flange connection with pressure measuring connection R 1/8
  • Lantern
  • Coupling
  • IEC standard motor
Scope of delivery
  • Pump
  • Installation and operating instructions
COUNTER FLANGE KIT DN65 PN10
Item no.: 2105583
Mating flanges:
  • Made of steel.
  • Counter flanges (weld) are delivered complete (in pairs) with bolt, nut and flange gasket.
Flange gasket DN 65 PN6/10
Item no.: 2151002
Flange gasket DN 65 PN6 / 10, Klingersil:
  • Thickness: 2 mm.
  • Inner diameter: 77 mm.
  • Outer diameter: 115 mm.
Difference pressure sensor 10 m
Item no.: 2136454

The differential pressure sensor kit enables dp-c and dp-v control of the frequency-controlled high-pressure centrifugal pumps.
The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
Difference pressure sensor 20 m
Item no.: 2136456

The differential pressure sensor kit enables dp-c and dp-v control of the frequency-controlled high-pressure centrifugal pumps.
The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
Difference pressure sensor 40 m
Item no.: 2136458

The differential pressure sensor kit enables dp-c and dp-v control of the frequency-controlled high-pressure centrifugal pumps.
The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
Difference pressure sensor 60 m
Item no.: 503184696

The differential pressure sensor kit enables dp-c and dp-v control of the frequency-controlled high-pressure centrifugal pumps.
The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
Difference pressure sensor 100 m
Item no.: 503184799

The differential pressure sensor kit enables dp-c and dp-v control of the frequency-controlled high-pressure centrifugal pumps.
The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
Frequency converter EFC 5,5 kW 3~
Item no.: 2551154