Existing pump - Circulation
Replacement pump - High Efficiency Premium Smart Exchange sheet
Comment
                Product information
                
                Stratos MAXO-D 40/0,5-8
                
            
        
                                                                    Your advantages
- Intuitive operation by means of application-guided settings with the Setup Guide plus the combination of a new display and operating button using Green Button Technology.
 - Maximum energy efficiency thanks to the combination of optimised and innovative energy-saving functions (e.g. No-Flow Stop).
 - Optimum system efficiency thanks to new and innovative intelligent control functions, such as Dynamic Adapt plus, Multi-Flow Adaptation, T-const. and ΔT-const.
 - Latest communication interfaces (e.g. Bluetooth) for connection to mobile devices and direct pump networking for multiple pump control via Wilo Net.
 - Maximum convenience in electrical installation thanks to a clearly arranged and spacious terminal room and the optimised Wilo-Connector.
 
More efficiency, connectivity and comfort than ever before – the Wilo-Stratos MAXO and the Wilo-Stratos MAXO-D deliver the future of pump technology to your doorstep. The world’s first smart-pump* features tomorrow’s innovations that make your life easier today.
Construction
Smart glandless twin-head circulator with screwed connection or flange connection, EC motor with integrated electronic power adjustment.
Application
Hot-water heating systems of all kinds, air-conditioning systems, closed cooling circuits, industrial circulation systems.
Equipment/function
Field of application:
The pump facilitates an operation with highest system efficiency via precise setting of the control mode for the system-specific application (e.g. radiator, underfloor heating, ceiling cooling).
Heating
- Radiator
 - Underfloor heating
 - Ceiling heating
 - Fan heater
 - Hydraulic shunt
 - Heat exchanger
 
- Ceiling cooling
 - Underfloor cooling
 - Air-conditioning devices
 - Hydraulic shunt
 - Heat exchanger
 
- Automatic switchover
 
Control modes:
- Constant speed (control mode)
 - Δp-c for constant differential pressure
 - Δp-v for variable differential pressure
 - Dynamic Adapt plus for continuous (dynamic) adjustment of the delivery rate to the current requirement
 - T-const. for constant temperature regulation
 - ΔT for differential temperature control
 - Constant Q for constant volume flow control
 - Multi-Flow Adaptation: Total volume flow determination through the feeder pump for the needs-based supply of secondary pumps in the heating circuit distributors
 - User-defined PID controller
 
- Q-limitmax. for limiting the maximum volume flow
 - Q-limitmin. for limiting the minimum volume flow
 - No-Flow Stop (zero-flow-deactivation)
 - Automatic setback operation
 - Index circuit evaluator (Δp-c control with external actual value sensor)
 - Thermal disinfection detection (Stratos MAXO-Z)
 - Variable pitch of Δp-v pump curve
 
- Selection of the field of application using the Setup Guide
 - Setting the related operating parameters
 - Nominal duty point: direct input of calculated duty point at Δp-v
 - Status display
 - Setting and resetting the energy meters (heating and cooling)
 - Pump venting function
 - Key lock for disabling the settings
 - Function for resetting the factory settings or the saved restoration points (parameter sets)
 - Parameterising the analogue inputs
 - Parameterising the binary inputs
 - Parameterising the relay outputs
 - Dual pump function (for 2 single pumps, which should be operated as twin-head pump)
 
- Power adjustment according to requirements for energy-efficient operation depending on the operating mode
 - Setback operation
 - Deactivation at zero flow (No-Flow Stop)
 - Soft start
 - Automatic troubleshooting routines (e.g. deblocking function)
 - Switchover heating/cooling mode
 - Full motor protection with integrated trip electronics
 
2 x analogue inputs:
- Signal types: 0 – 10 V, 2 – 10 V, 0 – 20 mA, 4 – 20 mA, PT1000
 - Applications: Remote adjustment of the setpoints in every control mode (except Multi-Flow Adaptation), sensor inputs for temperature, differential pressure or free sensor in user-defined PID-operating mode
 
- For potential-free control outputs or switch
 - Parametrizable functions:
 - Ext. Off
 - Ext. Min
 - Ext. Max
 - MANUAL (BMS-OFF)
 - Key lock
 - Switchover between heating/cooling mode
 
Signal and display functions
- Display status operation display:
 - Setpoint
 - Actual delivery head
 - Actual volume flow
 - Power consumption
 - Electric consumption
 - Temperatures
 - Status display LED: Faultless operation (green LED), pump communication (blue LED)
 - Display status of display fault (display red):
 - Error codes and error description in full text
 - Remedial measures
 - Display status of display warning (display yellow):
 - Warning codes and description of the warning in full text
 - Remedial measures
 - Display status process indicator (display blue):
 - Pump venting
 - Update procedure
 - Display BMS communication (display blue):
 - Summary of the active BMS parameters (baud rate, address,...)
 - Collective fault signal SSM (potential-free changeover contact)
 - Collective run signal SBM (potential-free normally open contact)
 
- Bluetooth interface for wireless data exchange and remote operation of the pump using a smartphone or tablet.
 - Serial digital interface Modbus RTU for connecting building automation (BA) via RS485 bus system (possible with Wilo-CIF module Modbus RTU).
 - Serial digital interface BACnet MS/TP for connecting building automation (BA) via RS485 bus system (possible with Wilo-CIF module BACnet MS/TP).
 - Serial digital interface LON for connecting building automation (BA) via bus system LONWorks (possible with Wilo-CIF module LON).
 - Serial digital interface PLR for connecting BA via company-specific coupling module (possible with Wilo-CIF module PLR).
 
- Main/standby operation (automatic fault-actuated switchover/time-sensitive pump alteration)
 - Parallel operation (efficiency-optimised peak load cut-in and out)
 
- For flange-end pumps: Flange versions
 - Standard version for DN 32 to DN 65 pumps: PN 6/10 combination flange (PN 16 flange according to EN 1092-2) for PN 6 and PN 16 counter flanges
 - Standard version for DN 80/DN 100 pumps: PN 6 flange (designed for PN 16 according to EN 1092-2) for PN 6 counter flange
 - Special version for DN 32 to DN 100 pumps: PN 16 flange (according to EN 1092-2) for PN 16 counter flange
 - Various integrated communication interfaces and optionally usable CIF module plug-in position
 - 5 cable inlets for connecting the communication interfaces
 - Bluetooth interface
 - High resolution graphic display with green button and 2 additional buttons
 - User-friendly terminal room
 - Integrated temperature sensor
 - Quick electrical connection with optimised Wilo-Connector for the power supply
 
- Pump
 - 2x optimised Wilo-Connector
 - 4x threaded cable connection M16 x 1.5
 - Washers for flange screws (for nominal connection diameters DN 32 - DN 65)
 - Gaskets for threaded connection
 - Installation and operating instructions
 
- Permissible temperature range -10 °C to +110 °C
 - Mains connection 1~230 V, 50/60 Hz
 - Protection class IPX4D
 - Screwed connection DN 30 (RP 11/4)
 - Flange connection DN 32 to DN 80
 - Max. operating pressure of standard version: 6/10 bar or 6 bar (special version: 10 bar or 16 bar)
 - Insulation class: F
 - Emitted interference in acc. with: EN 61800-3:2004+A1:2012 / residential environment (C1)
 - Interference resistance in acc. with: EN 61800-3:2004+A1:2012 / industrial environment (C2)
 
- Pump housing: grey cast iron with cataphoretic-coated
 - Shaft: Stainless steel
 - Bearing: carbon
 - Impeller: Plastic
 
- Smart glandless twin-head circulator with EC motor and integrated electronic power adjustment
 - Green Button Technology and graphic display
 - Motor protection with trip electronics
 - Plug connection for functional extension with optional CIF modules for building automation (BA)
 - Impeller with three-dimensionally curved blades and plastic sealing tube made of carbon fibre composite material
 
                                                            - Made of steel.
 - Counter flanges (weld) are delivered complete (in pairs) with bolt, nut and flange gasket.
 
                                                            - Comes in a complete kit containing a lid and gasket.
 
                                                            - Fits all Strato's MAXO pumps.
 
                                                            - Fits all Strato's MAXO pumps.
 
                                                            - Thickness: 2 mm.
 - Inner diameter: 49 mm.
 - Outer diameter: 85 mm.
 
                                                            Connection to Stratos Maxo to detect the fluid temperature in the case of temperature-dependent pump control or to detect heating/cooling quantities.
- Sensor Pt 1000 Class AA, ø6 x 40 mm
 - Cable length: 3 m
 - Measurement range: -5 °C to 70 °C, briefly up to 90 °C
 
                                                            Connection to Stratos Maxo-Z to detect the hot water outlet temperature on the reservoir to detect the thermal disinfection.
- Sensor Pt 1000 Class B, ø8.5 x 35 mm
 - Cable length 5 m
 - Measurement range -5 °C to 70 °C, briefly up to 90 °C.
 
                                                            For admission of the immersion sensor Pt 1000 AA for connection to Stratos MAXO.
- Thread: G 1/2
 - Inner Ø 6.4 mm for sensor to ø6 mm
 - Length of engagement 100 mm for installation in thread T-connector for use with pipes from approx. DN 65 to DN 100
 
                                                            For admission of the immersion sensor Pt 1000 AA for connection to Stratos MAXO.
- Thread: G 1/2
 - Inner Ø 6.4 mm for sensor to ø6 mm
 - Length of engagement 45 mm for installation in thread T-connector for use with pipes from DN 25 to approx. DN 50
 
                                                            General functions
Serial, digital interface for connection to building automation (BA) for the transfer of data points as:
- Control commands to the pump
 - Messages from the pump
 - Process values
 
                                                            General functions
Serial, digital interface for connection to building automation (BA) for the transfer of data points as:
- Control commands to the pump
 - Messages from the pump
 - Process values
 
                                                            General functions:
Serial, digital interface for connection to building automation (BA) for the transfer of data points as:
- Control commands to the pump
 - Messages from the pump
 - Process values
 
                                                            General functions:
Serial, digital interface for connection to building automation (BA) for the transfer of data points as:
- Control commands to the pump
 - Messages from the pump
 - Process values
 
                                                            Enables remote monitoring and control of connected products using the Wilo-Smart connect function in the Wilo Assistant app.
                                                            General functions
Serial, digital interface for connection to building automation (BA) for the transfer of data points as:
- Control commands to the pump
 - Messages from the pump
 - Process values
 
                                                            General functions:
Serial, digital interface for connection to building automation (BA) for the transfer of data points as:
- Control commands to the pump
 - Messages from the pump
 - Process values
 
                                                            Temperature sensor intended for Stratos MAXO -R7 and Stratos MAXO-D -R7 (threaded pumps).
Features:
- Operation via control mode T-const. and ΔT const.
 - Night setback
 - Measurement of heating and cooling energy
 - Automatic switching between heating / cooling
 
                                                            The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
                            
                            
                            Replacement pump - High Efficiency Standard Exchange sheet
Comment
                Product information
                
                Yonos MAXO-D 40/0,5-8
                
            
        
                                                                    Your advantages
- LED display provides complete transparency of set delivery head, speed stage or possible errors
 - Simple adjustment over three speed stages when replacing an uncontrolled standard pump
 - Easier electrical connection using the Wilo plug
 - System availability ensured via collective fault signal
 - Compact design and proven ease of use
 
Glandless circulator with flange connection, EC motor with automatic power adjustment.
Application
Hot-water heating systems of all kinds, air-conditioning systems, closed cooling circuits, industrial circulation systems.
Equipment/function
Operating modes:
- Δp-c for constant differential pressure
 - Δp-v for variable differential pressure
 
- Setting the operating mode
 - Setting of pump output (delivery head)
 
- Infinitely variable power adjustment according to the operating mode
 - Deblocking function
 - Soft start
 - Integrated full motor protection
 
- Collective fault signal (potential-free NC contact)
 - Fault signal light
 - LED segment display for displaying the delivery head and fault codes
 
- Main/standby operation: for an automatic fault-actuated switchover, a corresponding switchgear must be provided on-site
 - Predefined control mode and set delivery head must be identical for both pumps
 
- Wrench attachment point on pump body (for threaded pipe union pumps)
 - Quick electrical connection with Wilo plug. For the connection of the mains and SSM lines, with integrated strain relief
 - For flange-end pumps: Flange versions
 - Standard version for pumps DN 32 to DN 65: Combination flange PN 6/10 (flange PN 16 acc. to EN 1092-2) for counter flanges PN 6 and PN 16
 - Standard version for DN 80/DN 100 pumps: PN 6 flange (designed for PN 16 according to EN 1092-2) for PN 6 counter flange
 
- Pump
 - Incl. washers for flange screws (for nominal connection diameters DN 32 - DN 65)
 - Including installation and operating instructions
 
- Permissible temperature range of -20°C to +110°C
 - Mains connection 1~230 V, 50/60 Hz
 - Protection class IP X4D
 - Flange connection DN 32 to DN 80
 - Max. operating pressure of standard version: 6/10 bar or 6 bar (special version: 10 bar)
 
- Pump housing: grey cast iron with cataphoretic coating
 - Shaft: Stainless steel
 - Bearing: carbon, metal impregnated
 - Impeller: Plastic
 
                                                            - Made of steel.
 - Counter flanges (weld) are delivered complete (in pairs) with bolt, nut and flange gasket.
 
                                                            - Comes in a complete kit containing a lid and gasket.
 
                                                            - Thickness: 2 mm.
 - Inner diameter: 49 mm.
 - Outer diameter: 85 mm.
 
                                                            The Wilo-Connect module Yonos MAXO is installed on the electronic module of the pump at the position of the Wilo plug.
Utilisation of the Wilo-Connect moduleYonos MAXO dispenses with external contactors and other switchgears as well as the associated installation workload. The load of customer-side switchgears (relays) due to high starting currents is reduced to a minimum by the Connect module Yonos MAXO.
Equipment/function
- Run signal display
 - SSM collective fault signal as potential-free NC contact
 - SBM collective run signal as potential-free NO contact
 - Overriding Off control input (External Off)
 - Integrated dual pump management with the functions:
 - Main/standby operation with runtime-dependent (24 h) switchover from main to standby pump
 - Fault-sensitive switchover to operational standby pump