1 replacement option found

Existing pump - Circulation

Brand Salmson
Product name JRE 206-11/2,2
Overall length 340 mm
Mains connection 3x400 V
Pipe Connection DN 65 PN10

Circulation Circulation Exchange sheet

Product name DP-E 65/110-2,2/2
Item no. 2144216-2158951
Overall length 340 mm
Mains connection 3x400 V
Pipe Connection DN 65 PN16
Nominal power P2 2,2 kW

Comment

Fits without any modification of piping.
If you are pumping chilled water media or special material requirements, please contact Wilo Technical Inside Sales. Replacement pumps designed for glycolin-infused water (max. 50%) have the -S1 extension and a different part number than standard seal pumps. Always consult Wilo when pumping media other than water. 

Product information
DP-E 65/110-2,2/2

DP-E 65/110-2,2/2
Item no. : 2144216-2158951

Your advantages
  • Energy savings due to integrated electronic power adjustment
  • Optional interfaces for bus communication using plug-in IF-Modules
  • Simple operation with Green Button Technology and display
  • Integrated dual pump management
  • Integrated full motor protection (PTC thermistor sensor) with trip electronics
Construction
Electronically controlled glanded twin-head pump in in-line design with flange connection and automatic power adjustment.

Application
Pumping of heating water (acc. to VDI 2035), cold water and water/glycol mixtures without abrasive substances in heating, cold water and cooling systems.

Equipment/function
Operating modes:
  • Δp-c for constant differential pressure
  • Δp-v for variable differential pressure
  • PID control
  • Constant speed (n=constant)
Manual operation level
  • Green button and display
Manual functions
  • Differential pressure setpoint setting
  • Setting the speed (manual control mode)
  • Setting the operating mode
  • Setting the pump ON/OFF
  • Configuration of all operating parameters
  • Fault acknowledgement
External control functions
  • "Overriding Off" control input
  • “External pump cycling” control input (effective only in dual pump operation)
  • Analogue input 0 – 10 V, 0 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 2 – 10 V, 4 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 0 – 10 V for actual value signal from pressure sensor
  • Analogue input 2 – 10 V, 0 – 20 mA, 4 – 20 mA for actual value signal from pressure sensor
Signal and display functions
  • Collective fault signal SSM
  • Collective run signal SBM
Data exchange
  • Infrared interface for wireless data exchange with IR-Monitor/IR-Stick
  • Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation
Safety functions
  • Full motor protection with integrated trip electronics
  • Access disable
Dual pump management (twin-head pump or 2 x single pumps)
  • Main/standby operation (automatic fault-actuated switchover)
  • Pump cycling main/standby operation after 24 hours
  • Parallel operation
  • Parallel operation (efficiency-optimised peak-load activation and deactivation)
Scope of delivery
  • Pump
  • Installation and operating instructions
Technical data
  • Permissible temperature range -20 °C to +120 °C
  • Mains connection
  • 3~400 V ±10 %, 50 Hz
  • 3~380 V -5 % +10 %, 60 Hz
  • Protection class IP 55
  • Nominal diameter DN 32 to DN 80
  • Max. operating pressure 10 bar (special version: 16 bar)
Materials
  • Pump housing and lantern: EN-GJL-250
  • Impeller: PPO-GF30
  • Shaft: 1.4021
  • Mechanical seal: AQEGG; other mechanical seals on request
Description/construction
Single-stage, low-pressure twin-head pump in in-line design with: 
  • Switchover valve
  • Mechanical seal
  • Flange connection
  • Drive with integrated electronic speed control
Flange gasket DN 65 PN6/10
Item no.: 2151002
Flange gasket DN 65 PN6 / 10, Klingersil:
  • Thickness: 2 mm.
  • Inner diameter: 77 mm.
  • Outer diameter: 115 mm.