1 replacement option found

Existing pump - Circulation

Brand Flygt, ITT, Lowara, Xylem
Product name LNES 200-315/550
Overall length 900 mm
Mains connection 3x400 V
Pipe Connection DN 200 PN16
Nominal power P2 55 kW

Replacement pump - Conventional Exchange sheet

Product name Atmos GIGA-I 200/305-45/4
Item no. 2219196
MEI ≥ 0,4
IE 3
Overall length 820 mm
Mains connection 3x400 V
Pipe Connection DN 200 PN16
Rated Current 86,9 A
Nominal power P2 45 kW
Fluid temperature range -20 - +140 °C

Comment

Fits special replacement accessories.
Replacement pump has less motor power.
Check duty point.
If you are pumping chilled water media or special material requirements, please contact Wilo Technical Inside Sales. Replacement pumps designed for glycolin-infused water (max. 50%) have the -S1 extension and a different part number than standard seal pumps. Always consult Wilo when pumping media other than water. 

Product information
Atmos GIGA-I 200/305-45/4

Atmos GIGA-I 200/305-45/4
Item no. : 2219196

Design
Glanded pump in in-line design with flange connection.

Application
The pumping of heating water (in accordance with VDI 2035), chilled water and water-glycol mixtures without abrasive substances in heating, chilled water and cooling systems.

Technical data
  • Permitted temperature range of the fluid: -20 °C to +140 °C
  • Max. ambient temperature 40 °C
  • Mains connection 3~400 V, 50 Hz (others on request)
  • Protection class IP55
  • Nominal diameter DN 32 to DN 250
  • Standard version for operating pressure: 13 bar (up to +140 °C) / 16 bar (up to +120 °C)
Materials
  • Pump housing and lantern: Standard: EN-GJL-250;
  • Impeller: Standard: EN-GJL-200; special version: Bronze CuSn 10 stainless steel 1.4408
  • Shaft: 1.4122
  • Mechanical seal: AQEGG; other mechanical seals on request
Construction
Single-stage, low-pressure centrifugal pump in in-line design with:
  • Mechanical seal
  • Flange connection with pressure measuring connection R 1/8
  • Lantern
  • Coupling
  • IEC standard motor
Scope of delivery
  • Pump
  • Installation and operating instructions