1 replacement option found

Existing pump - Circulation

Brand Grundfos
Product name UPTD 100-120 PN6
Overall length 450 mm
Mains connection 3x400 V
Pipe Connection DN 100 PN6

Replacement pump - High Efficiency Premium Exchange sheet

Product name Stratos GIGA-D 100/1-13/2,3
Item no. 2170247
MEI ≥ 0,7
IE 5
Overall length 450 mm
Mains connection 3x400 V
Pipe Connection DN 100 PN16
Rated Current 4,7 A
Nominal power P2 2,3 kW
Fluid temperature range -20 - +140 °C

Comment

Pump flanges are drilled according to pressure class PN6.
If you are pumping chilled water media or special material requirements, please contact Wilo Technical Inside Sales. Replacement pumps designed for glycolin-infused water (max. 50%) have the -S1 extension and a different part number than standard seal pumps. Always consult Wilo when pumping media other than water. 

Product information
Stratos GIGA-D 100/1-13/2,3

Stratos GIGA-D 100/1-13/2,3
Item no. : 2170247

Your advantages
  • Innovative high-efficiency pump for maximum overall efficiency levels
  • High-efficiency EC motor with efficiency class IE5 according to IEC 60034-30-2
  • Highest possible operational reliability thanks to standby pump
  • Optional interfaces for connection to building automation using insertable IF modules
Maximum energy efficiency, double safety.

The Wilo-Stratos GIGA is the ideal high-efficiency pump for use in heating, air conditioning and cooling applications in buildings where large volumes of water have to be pumped to great delivery heights. Wilo-Stratos GIGA offers ever greater operational reliability with the standby pump in the twin-head pump version.

Construction
High-efficiency in-line twin-head pump with EC motor and electronic power adjustment in glanded pump construction. Version as single-stage low-pressure centrifugal pump with flange connection and mechanical seal.

Application
The pumping of heating water (in accordance with VDI 2035), cold water and water-glycol mixtures without abrasive substances in heating, cold water and cooling systems.

Equipment/function
Operating modes
  • Δp-c for constant differential pressure
  • Δp-v for variable differential pressure
  • PID-Control
  • Constant speed (n=constant)
Manual operation level
  • Green button and display
Manual functions
  • Differential pressure setpoint setting
  • Setting the speed (manual control mode)
  • Setting the operating mode
  • Setting the pump ON/OFF
  • Configuration of all operating parameters
  • Fault acknowledgement
External control functions
  • "Overriding Off" control input
  • “External pump cycling” control input (only effective in twin-head pump operation)
  • Analogue input 0 – 10 V, 0 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 2 – 10 V, 4 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 0 – 10 V for actual value signal from pressure sensor
  • Analogue input 2 – 10 V, 0 – 20 mA, 4 – 20 mA for actual value signal from pressure sensor
Signal and display functions
  • Collective fault signal SSM
  • Collective run signal SBM
Data exchange
  • Infrared interface for wireless data exchange with IR-Monitor/IR-Stick
  • Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation
Safety functions
  • Full motor protection with integrated trip electronics
  • Access disable
Dual pump management (twin-head pump or 2 x single pumps)
  • Main/standby operation (automatic fault-actuated switchover)
  • Pump cycling main/standby operation after 24 hours
  • Parallel operation
  • Parallel operation (efficiency-optimised peak-load activation and deactivation)
Scope of delivery
  • Pump
  • Installation and operating instructions
  • Technical data 
  • Permitted temperature range of the fluid: -20 °C to +140 °C
  • Mains connection 3~480 V ±10 %, 50/60 Hz, 3~440 V ±10 %, 50/60 Hz, 3~400 V ±10 %, 50/60 Hz, 3~380 V -5 % +10 %, 50/60 Hz
  • Protection class IP55
  • Nominal diameter DN 40 to DN 100
  • Max. operating pressure 16 bar
Materials
  • Pump housing and lantern: EN-GJL-250
  • Impeller: PPS-GF40 or EN-GJL-200 depending on the type
  • Shaft: 1.4122
  • Mechanical seal: AQEGG; other mechanical seals on request
Flange gasket DN 100 PN6/10
Item no.: 2153115
Flange gasket DN 100 PN6 / 10, Klingersil:
  • Thickness: 2 mm.
  • Inner diameter: 115 mm.